《低压电气装置 第4-41部分:安全防护 电击防护》GB/T 16895.21-2020/IEC 60364-4-41:2017 Low-voltage electrical installations Part 4 – 41:Protection for safety –Protection against electric shock,4次提到“不超过30mA”RCD的设置要求,且均为附加防护!分别如下:
411.1 通则
Where specified, additional protection is provided by a residual current protective device (RCD) with rated residual operating current not exceeding 30 mA in accordance with 415.1.
当有具体规定时,可采用符合415.1条要求的额定剩余电流动作值不超过30mA的剩余电流动作保护电器(RCD)作附加防护措施。
411.3.3 用于插座和户外移动设备的供电更进一步的要求
Further requirements for socket-outlets and for the supply of mobile equipment for use outdoors
Additional protection by means of a residual current protective device (RCD) with a rated residual operating current not exceeding 30 mA shall be provided for
◆a.c. socket-outlets with a rated current not exceeding 32 A that are liable to be used by ordinary persons and are intended for general use; and
◆a.c. mobile equipment for use outdoors with a rated current not exceeding 32 A.
额定动作电流不超过30mA的剩余电流动作保护电器(RCD)作为附加防护用于:
①供一般人员用普通用途的额定电流不超过32A的交流插座,和
②供户外额定电流不超过32A的交流移动式设备。
411.3.4 在TN和TT系统中用于照明回路的附加要求
Additional requirements for circuits with luminaires in TN- and TT-systems
In premises designed to accommodate a single household, additional protection by a residual current protective device (RCD) with a rated residual operating current not exceeding 30 mA shall be provided for a.c.final circuits supplying luminaires.
对于单独住户的房屋向照明供电的交流终端回路,应提供额定剩余动作电流不超过30mA的剩余电流动作保护电器(RCD) 作为附加防护。
415.1.1 在交流系统内装设额定剩余电流不大于30mA的RCD,用以在基本防护失效和/或故障保护或用电不慎时的附加防护措施。
The use of RCDs with a rated residual operating current not exceeding 30 mA, is recognized in a.c. systems as additional protection in the event of failure of the provision for basic protection and/or the provision for fault protection or carelessness by users.
结论
①拥于保护人身安全的RCD作为电击防护的附加防护措施,其额定剩余电流动作值都不应大于30mA。
②国标与IEC标准是一脉相承的!
作者:李炳华(“鸟巢”电气总设计师)